Wiring multiple...MFT actuators to single shaft and/or on
valves. All MFT actuators are wired in master-slave
configuration.
MFT actuator configurations should also co-ordinate with
each other. Meaning the master input = controllers output.
Master output = slave input. Slave output = controller input.
EFB24-MFT(-S)
EFX24-MFT(-S)
3
810 in-lb
432 in-lb
Controller
Output
Slave
Input
Slave
Feedback
Master
Feedback
2 to 10 VDC2 to 10 VDC 2 to 10 VDC 0 to 5 VDC
Equipment damage!
Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input
impedance must be observed.
4
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Hazard Identification
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.
Actuators with plenum rated cable do not have numbers on
wires; use color codes instead. Actuators with appliance
cables are numbered.
3
Actuators may also be powered by 24 VDC.
5
21
INSTALLATION NOTES
Provide overload protection and disconnect as required.
23
Consult controller instruction data for more detailed
information.
25
To reverse control rotation, use the reversing switch.
Blk (1) Common
Red (2) + Hot
Wht (3) Y
Input, 2 to 10 V
Org (5) U Output 2 to 10 V
CCW CW
Master
CCW CW
Slave
24 VAC Transformer
Line
Volts
Control Signal
2 to 10 VDC or
4 to 20 mA
500 Ω
1/4 watt
(–)
(+)
3
5
4
Maximum
4 actuators
per shaft.
Blk (1) Common
Red (2) + Hot
Wht (3) Y
Input, 2 to 10 V
Org (5) U
5
5
5
Multiple Actuators Mounted to One Control Shaft
VDC or 4-20mA
Blk (1) Common
Red (2) + Hot
Wht (3) W
Pnk
(4) R
Gry (5) B
Org (6) U Output,
2 to 10 V
Master
CCW CW
Slave
-MFT95
-MFT
24 VAC Transformer
Line
Volts
3
21
23
25
23
25
4
Blk (1) Common
Red (2) + Hot
Wht (3) Y
1
Input
Pnk (4) Y
2
Input
Org (6) U
Output 2 to 10 V
W
R
B
Control Type: VDC or 4-20mA MFT95
Example
Multiple Actuators Mounted to One Control Shaft
Model Max. Qty Per Shaft Torque Generated
W234_2_B_11
3
GMX(B)24-MFT
GKX(B)24-MFT
AFB24-MFT(-S)
AFX24-MFT(-S)
2
2
640 in-lb
640 in-lb
Wiring for Damper Actuators and Control Valves
Wiring Multiple MFT Actuators